Table 1: Auotune calibration surpasses ASHRAE G14 requirements. Results from a 20,000+ building calibration study, involving building types representing 80% of U.S. Commercial Floor Space and 47-470 tunable inputs each, show predication of building electrical use within 4%.
ASHRAE G14 Requires Autotune Results
Monthly utility data CV(RMSE) 15% 1.20%
NMBE 5% 0.35%
Hourly utility data CV(RMSE) 30% 3.65%
NMBE 10% 0.35%